The SBW series three-phase fully automatic compensated power voltage regulator is suitable for applications where voltage fluctuations are caused by variations in the external power grid voltage or load changes. It automatically maintains a stable output voltage. Compared with other types of voltage regulators, this series offers advantages such as large capacity, high efficiency, no waveform distortion, and smooth voltage regulation. It is suitable for a wide range of loads, can withstand instantaneous overload, and can operate continuously for long periods. It supports manual/automatic switching and is equipped with overvoltage protection, phase loss protection, phase sequence protection, and automatic protection against mechanical failures. In addition, the unit features a compact size, light weight, easy installation, and reliable operation.
-Input Voltage Range: 3PH 304V-456V customizable
-Output Voltage: 3PH 380V
-Rated Power: 50 KVA -2000 KVA
-Voltage Accuracy: (2-5%) Adjustable
-Frequency: 50-60Hz
-Response Time: ≤1.5s (When external voltage changes by 10%)
-Waveform Distortion: No additional waveform distortion
-Efficiency: ≥90% (Power rating above 50KVA)
-Mains Bypass: Convenient switching between mains supply and stabilized output for three-phase products
-Starting Method: Automatic startup on power-up or manual startup selectable
-Operating Mode: Can operate continuously unattended for long periods
-Protection Features: Overvoltage protection, overcurrent protection, phase loss and phase sequence protection for units above 150KVA
▌Voltage Stabilizer Functions Features:
▌Protection Function:
☑Overload Protection:
When the load power reaches 120%, the voltage stabilizer automatically activates protection, cutting off the output.
☑Overvoltage Protection:
When the output phase voltage exceeds 250V, the overvoltage indicator lights up, and the output is automatically cut off.
☑Undervoltage Protection:
When the output voltage drops below 184V, the undervoltage indicator lights up, and the output is automatically cut off.
☑Delay Protection:
Upon power-up, a delay of several seconds is automatically initiated before voltage stabilization begins.
☑Short Circuit Protection:
When a short circuit occurs, the voltage stabilizer automatically stops output and requires manual reset to restore output.
☑Over temperature protection:
Over-temperature protection will shut down the regulator if it exceeds a safe operating temperature, preventing damage to its internal circuitry.
▌Product Characteristics:
Effective energy saving via 3 copper core voltage regulating columns & 3 high-power voltage stabilizing compensation coils.
Dual microcomputer control board, one-key switching of the main control board, quickly resolving faults.
Manual/automatic conversion key, easily switching between manual and automatic output modes.
Mains/stabilized flexible voltage switch providing mains direct and stabilized dual-mode functions.
Electric operating mechanism combined with 1017 carbon brushes, achieving precise and stable output voltage.
Adopts high-quality silver point AC contactor, energy-saving and noise-free, long-lasting and reliable.
▌Application:
Our SBW voltage regulator can be widely used in: industrial and mining enterprises, oil fields, railways, construction sites, schools, hospitals, posts and telecommunications, hotels, scientific research and other departments of electronic computers, precision machine tools, computed tomography (CT), precision instruments, test equipment, elevator lighting, imported equipment and production lines and other places that need stable voltage power supply. It is also suitable for users at the end of the low-voltage distribution network where the power supply voltage is too low or too high, and the fluctuation range is large, and the electrical equipment with large load changes, especially for all the places where the power grid waveform is required to be high. High power compensation type power regulator can be connected to fire, hydraulic, small generators.
Input | ||||
Input voltage | 220V/380V,230V/400V,240V/415V etc or other voltages accepted | |||
Phase | 3P+N+G or 3P+G option | |||
Input range | ±20%(±15% ~ ±60%) can be customized | |||
Input frequency | 47Hz-63Hz | |||
Input switch | Chint Brand switch(ABB,Schneider option) | |||
Output | ||||
Output voltage | 220V/380V,230V/400V,240V/415V etc or other voltages accepted | |||
Phase | 3P+N+G or 3P+G option | |||
Output accuracy | ±1%~±5%(factory setting 2%) | |||
Output Frequency | 50Hz/60Hz (LCD display will be identify automatc 50 or 60Hz) | |||
Power factor | 0.85 | |||
Waveform distortion | No distortion(same as input waveform) | |||
Efficiency | ≥98%(on full load) | |||
Overload capacity | 150% for 5 minutes,200% for 1 minute | |||
Response time | <10ms | |||
THD | <3%(linear load) | |||
General | ||||
Compensation transformer | Insulation H level,200 degree | |||
Control method | Compensation regulation or Independent regulation for each phase (option) | |||
Working principle | Full automatic ,servo motor/SCR/IGBT | |||
IP level | IP21(indoor), IP54 or IP65(Outdoor) | |||
Cooling | Air cooling/ Fan system | |||
Environment | ||||
Woking temperature | -20° to +50°(if high teperature in your city,please inform us) | |||
Ralative humidity | <90% | |||
Noise | 45db@70% load,55db@100%load (within one meter) | |||
Altitude | <1500m(if high attitude requried,please inform us) | |||
LCD display (Optional) | ||||
Display | 5.0 LCD digital dispaly | |||
LCD display show | Input Phase to netural | |||
Input phase to phase | ||||
Output phase to neutral | ||||
Output phase to phase | ||||
Load Current in each phases(press button to switch ) | ||||
Frequency (50 or 60hz autoamtic indentify show) | ||||
Working temperature | ||||
Function | ||||
Multi-functions | Malti-protect fuction,over voltage/under voltage protection,over current protection,over load protection,soft start protection,manual bypass protection(or automatic bypass),short circuit protection,lack of phase protection,wrong sequence protection,indicate alarm,over temperature protection. |
Model (kVA) | Rated Capacity | Net Weight | Dimensions |
KVA | KG | CM | |
SBW-50KVA/60 | 50 | 240 | 800 × 560 × 1200 |
SBW-80KVA | 80 | 280 | 800× 560 × 1200 |
SBW-100KVA | 100 | 320 | 850 x 620 x1250 |
SBW-120KVA | 120 | 330 | 850 x 620 x1250 |
SBW-150KVA | 150 | 460 | 900 x 700 x 1400 |
SBW-200KVA | 200 | 480 | 900 x 700 x 1400 |
SBW-250KVA | 250 | 580 | 1000 x 700 x 1550 |
SBW-300KVA | 300 | 660 | 850 × 1100 × 1650 |
SBW-350KVA | 350 | 730 | 850 × 1100 × 1650 |
SBW-400KVA | 400 | 780 | 850 × 1100 × 1650 |
SBW-500KVA | 500 | 1050 | 1000 × 1200 × 1800 |
SBW-600KVA | 600 | 1100 | 1000 x 1200 x1800 |
SBW-800KVA | 800 | 1750 | 1650 × 1150 × 1800 |
SBW-1000KVA | 1000 | 2200 | 1800 x 1250 x 1900 |
SBW-1200KVA | 1200 | 2300 | 1800 × 1250 × 1900 |
SBW-800KVA | 800 | 1950 | 750 x 1150 x 1800 |
SBW-1000KVA | 1000 | 2300 | 800 x 1250 x 1900 |
SBW-1200KVA | 1200 | 2500 | 800 x 1250 x 1900 |
SBW-1500/1600KVA | 1500/1600 | 3300 | 1100 x 1250 x 2000 |
SBW-2000KVA | 2000 | 4400 | 1200 x 1300 x 2000 |